ProAudio: Setting Up the Paging System (PuTTY / Direct Commands)

Modified on Wed, 22 Jul at 5:34 PM

When a page or doorbell is triggered, every zone switches to a predetermined source and volume, then returns to normal operation once the page ends. This article covers configuring paging by sending ASCII commands directly over serial or TCP/IP — for example, using PuTTY.

Configuring via a Control4 driver instead? See ProAudio: Setting Up the Paging System (Control4)
Configuring via the ProAudio Config Tool instead? See ProAudio — Setting Up Paging Using the Config Tool

How Paging Works

Every ProAudio switch has two independent page presets — Page 1 and Page 2 — each with its own configuration. For example, Page 1 could be used for the front door and Page 2 for the back door. If you have two different sound generators, you can connect each one to a different source and assign it to a different page preset.

The examples below assume a 16-zone switch, with input 15 as the doorbell chime source and a switch or relay wired to DB-1. Adjust the zone range to match your model — for example, change @1:16 to @1:32 on a 32-zone switch.

Wiring the Trigger Switch

Page 1 is triggered by the DB-1 input, and Page 2 by DB-2. Both accept a dry contact closure — a relay or push-button switch wired to the back of the switch.

Dry contact closure wiring for DB-1 and DB-2. SW-1 and SW-2 are chassis ground — connect a grounded cable's ground side there.

Setting Up Page 1

Run through these steps once for each page you want to configure. This example configures Page 1, triggered by DB-1.

1
Set the paging source.
^pASZ 1,@1:16,15$
Sets zones 1–16 to switch to source 15 (the doorbell chime input) whenever Page 1 is triggered.
2
Set the paging volume.
^pVPZ 1,@1:16,40$
Sets the Page 1 volume for zones 1–16 to 40% (0–100% scale). Use pVZ instead of pVPZ if you'd rather set the level in dB.
3
Unmute the zones for the page.
^pVMZ 1,@1:16,0$
Makes sure zones 1–16 come on during the page, overriding any existing mute state on the zone.
4
Allow the zones to respond to the page.
^pADNDZ 1,@1:16,0$
Sets the Do Not Disturb flag to 0 ("allow paging") for zones 1–16 on Page 1.
This step is not optional. Every zone defaults to Do Not Disturb = 1 (ignore paging). If you skip the pADNDZ command above, Page 1 will trigger correctly but every zone will silently ignore it — there's no error, the zones simply won't switch.
5
Configure the back panel trigger.
^pDSW 1,1,1,0$
Sets switch input 1 (DB-1) to trigger Page 1 in "Active on" mode — the page runs for as long as the contact stays closed. The final 0 is the timed-mode duration parameter, which "Active on" mode ignores, but the switch still expects it to be present.
6
(Optional) Set paging delays.
^pTIME 1,0,0$
Sets the initial delay and minimum page time for Page 1, both in milliseconds. The initial delay (first value) can hold off switching sources — useful for giving a power amp time to turn on. The minimum time (second value) guarantees a page lasts at least that long even if the trigger is only tapped briefly. Leave both at 0 if you don't need them.

Setting Up Page 2

Repeat the same six steps using preset 2 and DB-2:

^pASZ 2,@1:16,15$ 
^pVPZ 2,@1:16,40$ 
^pVMZ 2,@1:16,0$ 
^pADNDZ 2,@1:16,0$ 
^pDSW 2,1,2,0$ 
^pTIME 2,0,0$

Removing a Zone From Paging Temporarily

To exclude a single zone from a page — for example, to keep a page from waking a sleeping baby — set that zone's Do Not Disturb flag back to 1:

^pADNDZ 1,@5,1$    
zone 5 ignores Page 1 
^pADNDZ 1,@5,0$    
re-enable zone 5 for Page 1
There's also a middle option: setting the flag to 2 lets the zone respond to the page's volume and mute settings without switching its source — useful if you want a zone to duck in volume during a page but not actually play the doorbell chime.

Backing Up Your Settings

Back up after every change.Once both pages are configured, send:
^SS 4096$
This saves your paging settings to EEPROM. Without it, a power outage can silently wipe your configuration.

Triggering a Page Manually

If your controller can send ASCII strings, you can trigger a page directly instead of wiring up a physical switch:

^pSET 1$    
start Page 1 

^pSET 0$   
end the page and return to normal

Or trigger a page for a fixed duration, in milliseconds, and let it end automatically:

^pSET 1,4000$    
ring for 4 seconds, then return to normal automatically
Every page has a hard limit of two minutes, whether triggered by a switch or a command. If a page is left running longer than that — for example, a contact held closed, or a pSET 1$ without a follow-up pSET 0$ — it will automatically time out and return to normal.

Testing the Paging System

1
Trigger the page.Press the DB-1 switch, or send ^pSET 1$.
2
Check the zones.Zones 1–16 should switch to source 15 and rise to 40% volume.
3
End the page.Release the switch, or send ^pSET 0$. Zones should return to their previous source and volume.

If zones don't respond, double-check that their Do Not Disturb flag is set to "allow paging" (0) — this is the most common reason a page appears to do nothing.


Related Articles

Need help with your paging setup?

Our support team can help troubleshoot command syntax or wiring issues.

UK: 01202 413 610 | US: (858) 748-8250 | support@pulse-eight.com


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article